{"id":3807,"date":"2023-02-10T15:55:07","date_gmt":"2023-02-10T15:55:07","guid":{"rendered":"https:\/\/mmcarnot.com\/?p=3807"},"modified":"2023-05-19T19:00:55","modified_gmt":"2023-05-19T19:00:55","slug":"mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps","status":"publish","type":"post","link":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/","title":{"rendered":"M&#038;M Carnot organise un webinaire pour l&rsquo;Open Compute Project sur les pompes \u00e0 chaleur CO<sub>2<\/sub> \u00e0 r\u00e9utilisation de chaleur"},"content":{"rendered":"\n<p>L&rsquo;efficacit\u00e9 de l&rsquo;ITE et de la conception des centres de donn\u00e9es n&rsquo;est qu&rsquo;un des facteurs permettant de minimiser l&#8217;empreinte carbone associ\u00e9e \u00e0 la consommation d&rsquo;\u00e9nergie d&rsquo;un centre de donn\u00e9es &#8211; l&rsquo;utilisation de ressources renouvelables et la r\u00e9utilisation de l&rsquo;\u00e9nergie r\u00e9siduelle peuvent \u00e9galement avoir un impact positif.<\/p>\n\n\n\n<figure class=\"wp-block-image size-full is-resized\"><img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\" alt=\"\" class=\"wp-image-894\" width=\"143\" height=\"143\" srcset=\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png 285w, https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x-200x200.png 200w\" sizes=\"auto, (max-width: 143px) 100vw, 143px\" \/><\/figure>\n\n\n\n<p>Presque 100 % de l&rsquo;\u00e9nergie utilis\u00e9e dans un processeur est transform\u00e9e en chaleur.<\/p>\n\n\n\n<p>Jusqu&rsquo;\u00e0 tr\u00e8s r\u00e9cemment, cela repr\u00e9sentait un handicap et un d\u00e9fi, une immense quantit\u00e9 de chaleur devant \u00eatre \u00e9limin\u00e9e, ce qui n\u00e9cessitait encore plus d&rsquo;\u00e9nergie. Avec une conception appropri\u00e9e, les syst\u00e8mes de refroidissement des centres de donn\u00e9es peuvent \u00eatre transform\u00e9s en source de chaleur et en opportunit\u00e9 de gestion de la chaleur qui, \u00e0 son tour, transforme la chaleur d&rsquo;un passif en un actif.<\/p>\n\n\n\n<p>Le sous-groupe \u00ab\u00a0R\u00e9utilisation de la chaleur\u00a0\u00bb de l&rsquo;OCP \u00e9tudie ces d\u00e9fis et ces possibilit\u00e9s. Son objectif est de proposer des solutions pour faciliter la mise en \u0153uvre de technologies visant \u00e0 exploiter la chaleur et \u00e0 la transformer en profit plut\u00f4t qu&rsquo;en co\u00fbt. Ce projet est ouvert au public et nous accueillons tous ceux qui souhaitent y participer.<\/p>\n\n\n\n<p><\/p>\n","protected":false},"excerpt":{"rendered":"<p>L&rsquo;efficacit\u00e9 de l&rsquo;ITE et de la conception des centres de donn\u00e9es n&rsquo;est qu&rsquo;un des facteurs permettant de minimiser l&#8217;empreinte carbone associ\u00e9e \u00e0 la consommation d&rsquo;\u00e9nergie d&rsquo;un centre de donn\u00e9es &#8211; l&rsquo;utilisation de ressources renouvelables et la r\u00e9utilisation de l&rsquo;\u00e9nergie r\u00e9siduelle peuvent \u00e9galement avoir un impact positif. Presque 100 % de l&rsquo;\u00e9nergie utilis\u00e9e dans un processeur est transform\u00e9e en chaleur. Jusqu&rsquo;\u00e0 tr\u00e8s r\u00e9cemment, cela repr\u00e9sentait un handicap et un d\u00e9fi, une immense quantit\u00e9 de chaleur devant \u00eatre \u00e9limin\u00e9e, ce qui n\u00e9cessitait encore plus d&rsquo;\u00e9nergie. Avec une conception appropri\u00e9e, les syst\u00e8mes de refroidissement des centres de donn\u00e9es peuvent \u00eatre transform\u00e9s en source de chaleur et en opportunit\u00e9 de gestion de la chaleur qui, \u00e0 son tour, transforme la chaleur d&rsquo;un passif en un actif. Le sous-groupe \u00ab\u00a0R\u00e9utilisation de la chaleur\u00a0\u00bb de l&rsquo;OCP \u00e9tudie ces d\u00e9fis et ces possibilit\u00e9s. Son objectif est de proposer des solutions pour faciliter la mise en \u0153uvre de technologies visant \u00e0 exploiter la chaleur et \u00e0 la transformer [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[50],"tags":[],"class_list":["post-3807","post","type-post","status-publish","format-standard","hentry","category-evenement"],"acf":[],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v27.0 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>M&amp;M Carnot organise un webinaire pour l&#039;Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\" \/>\n<meta property=\"og:locale\" content=\"fr_FR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"M&amp;M Carnot organise un webinaire pour l&#039;Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot\" \/>\n<meta property=\"og:description\" content=\"L&rsquo;efficacit\u00e9 de l&rsquo;ITE et de la conception des centres de donn\u00e9es n&rsquo;est qu&rsquo;un des facteurs permettant de minimiser l&#8217;empreinte carbone associ\u00e9e \u00e0 la consommation d&rsquo;\u00e9nergie d&rsquo;un centre de donn\u00e9es &#8211; l&rsquo;utilisation de ressources renouvelables et la r\u00e9utilisation de l&rsquo;\u00e9nergie r\u00e9siduelle peuvent \u00e9galement avoir un impact positif. Presque 100 % de l&rsquo;\u00e9nergie utilis\u00e9e dans un processeur est transform\u00e9e en chaleur. Jusqu&rsquo;\u00e0 tr\u00e8s r\u00e9cemment, cela repr\u00e9sentait un handicap et un d\u00e9fi, une immense quantit\u00e9 de chaleur devant \u00eatre \u00e9limin\u00e9e, ce qui n\u00e9cessitait encore plus d&rsquo;\u00e9nergie. Avec une conception appropri\u00e9e, les syst\u00e8mes de refroidissement des centres de donn\u00e9es peuvent \u00eatre transform\u00e9s en source de chaleur et en opportunit\u00e9 de gestion de la chaleur qui, \u00e0 son tour, transforme la chaleur d&rsquo;un passif en un actif. Le sous-groupe \u00ab\u00a0R\u00e9utilisation de la chaleur\u00a0\u00bb de l&rsquo;OCP \u00e9tudie ces d\u00e9fis et ces possibilit\u00e9s. Son objectif est de proposer des solutions pour faciliter la mise en \u0153uvre de technologies visant \u00e0 exploiter la chaleur et \u00e0 la transformer [&hellip;]\" \/>\n<meta property=\"og:url\" content=\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\" \/>\n<meta property=\"og:site_name\" content=\"M&amp;M Carnot\" \/>\n<meta property=\"article:published_time\" content=\"2023-02-10T15:55:07+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2023-05-19T19:00:55+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\" \/>\n<meta name=\"author\" content=\"Mike Atkins\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u00c9crit par\" \/>\n\t<meta name=\"twitter:data1\" content=\"Mike Atkins\" \/>\n\t<meta name=\"twitter:label2\" content=\"Dur\u00e9e de lecture estim\u00e9e\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#article\",\"isPartOf\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\"},\"author\":{\"name\":\"Mike Atkins\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd\"},\"headline\":\"M&#038;M Carnot organise un webinaire pour l&rsquo;Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur\",\"datePublished\":\"2023-02-10T15:55:07+00:00\",\"dateModified\":\"2023-05-19T19:00:55+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\"},\"wordCount\":230,\"image\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\",\"articleSection\":[\"\u00c9v\u00e9nement\"],\"inLanguage\":\"fr-FR\"},{\"@type\":\"WebPage\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\",\"url\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\",\"name\":\"M&M Carnot organise un webinaire pour l'Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot\",\"isPartOf\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\",\"datePublished\":\"2023-02-10T15:55:07+00:00\",\"dateModified\":\"2023-05-19T19:00:55+00:00\",\"author\":{\"@id\":\"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd\"},\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage\",\"url\":\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\",\"contentUrl\":\"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png\"},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/#website\",\"url\":\"https:\/\/mmcarnot.com\/fr\/\",\"name\":\"M&amp;M Carnot\",\"description\":\"We&#039;re on a mission to cool the world.\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/mmcarnot.com\/fr\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"fr-FR\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd\",\"name\":\"Mike Atkins\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/f2dfa6f4c976c39d35f56a9c1a3c445c1262f1c4730697fc3cad664e1e9fad3f?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/f2dfa6f4c976c39d35f56a9c1a3c445c1262f1c4730697fc3cad664e1e9fad3f?s=96&d=mm&r=g\",\"caption\":\"Mike Atkins\"},\"url\":\"https:\/\/mmcarnot.com\/fr\/author\/mikeatkins\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"M&M Carnot organise un webinaire pour l'Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/","og_locale":"fr_FR","og_type":"article","og_title":"M&M Carnot organise un webinaire pour l'Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot","og_description":"L&rsquo;efficacit\u00e9 de l&rsquo;ITE et de la conception des centres de donn\u00e9es n&rsquo;est qu&rsquo;un des facteurs permettant de minimiser l&#8217;empreinte carbone associ\u00e9e \u00e0 la consommation d&rsquo;\u00e9nergie d&rsquo;un centre de donn\u00e9es &#8211; l&rsquo;utilisation de ressources renouvelables et la r\u00e9utilisation de l&rsquo;\u00e9nergie r\u00e9siduelle peuvent \u00e9galement avoir un impact positif. Presque 100 % de l&rsquo;\u00e9nergie utilis\u00e9e dans un processeur est transform\u00e9e en chaleur. Jusqu&rsquo;\u00e0 tr\u00e8s r\u00e9cemment, cela repr\u00e9sentait un handicap et un d\u00e9fi, une immense quantit\u00e9 de chaleur devant \u00eatre \u00e9limin\u00e9e, ce qui n\u00e9cessitait encore plus d&rsquo;\u00e9nergie. Avec une conception appropri\u00e9e, les syst\u00e8mes de refroidissement des centres de donn\u00e9es peuvent \u00eatre transform\u00e9s en source de chaleur et en opportunit\u00e9 de gestion de la chaleur qui, \u00e0 son tour, transforme la chaleur d&rsquo;un passif en un actif. Le sous-groupe \u00ab\u00a0R\u00e9utilisation de la chaleur\u00a0\u00bb de l&rsquo;OCP \u00e9tudie ces d\u00e9fis et ces possibilit\u00e9s. Son objectif est de proposer des solutions pour faciliter la mise en \u0153uvre de technologies visant \u00e0 exploiter la chaleur et \u00e0 la transformer [&hellip;]","og_url":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/","og_site_name":"M&amp;M Carnot","article_published_time":"2023-02-10T15:55:07+00:00","article_modified_time":"2023-05-19T19:00:55+00:00","og_image":[{"url":"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png","type":"","width":"","height":""}],"author":"Mike Atkins","twitter_card":"summary_large_image","twitter_misc":{"\u00c9crit par":"Mike Atkins","Dur\u00e9e de lecture estim\u00e9e":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#article","isPartOf":{"@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/"},"author":{"name":"Mike Atkins","@id":"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd"},"headline":"M&#038;M Carnot organise un webinaire pour l&rsquo;Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur","datePublished":"2023-02-10T15:55:07+00:00","dateModified":"2023-05-19T19:00:55+00:00","mainEntityOfPage":{"@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/"},"wordCount":230,"image":{"@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage"},"thumbnailUrl":"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png","articleSection":["\u00c9v\u00e9nement"],"inLanguage":"fr-FR"},{"@type":"WebPage","@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/","url":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/","name":"M&M Carnot organise un webinaire pour l'Open Compute Project sur les pompes \u00e0 chaleur CO2 \u00e0 r\u00e9utilisation de chaleur - M&amp;M Carnot","isPartOf":{"@id":"https:\/\/mmcarnot.com\/fr\/#website"},"primaryImageOfPage":{"@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage"},"image":{"@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage"},"thumbnailUrl":"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png","datePublished":"2023-02-10T15:55:07+00:00","dateModified":"2023-05-19T19:00:55+00:00","author":{"@id":"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd"},"inLanguage":"fr-FR","potentialAction":[{"@type":"ReadAction","target":["https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/"]}]},{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/mmcarnot.com\/fr\/evenement\/mm-carnot-hosts-a-webinar-for-the-open-compute-project-focusing-on-heat-reuse-co2-heat-pumps\/#primaryimage","url":"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png","contentUrl":"https:\/\/mmcarnot.com\/wp-content\/uploads\/2023\/02\/OCP-datacenter-v1-17a3x.png"},{"@type":"WebSite","@id":"https:\/\/mmcarnot.com\/fr\/#website","url":"https:\/\/mmcarnot.com\/fr\/","name":"M&amp;M Carnot","description":"We&#039;re on a mission to cool the world.","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/mmcarnot.com\/fr\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"fr-FR"},{"@type":"Person","@id":"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/a343b9312d6b147884dd1e1a93ae99cd","name":"Mike Atkins","image":{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/mmcarnot.com\/fr\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/f2dfa6f4c976c39d35f56a9c1a3c445c1262f1c4730697fc3cad664e1e9fad3f?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/f2dfa6f4c976c39d35f56a9c1a3c445c1262f1c4730697fc3cad664e1e9fad3f?s=96&d=mm&r=g","caption":"Mike Atkins"},"url":"https:\/\/mmcarnot.com\/fr\/author\/mikeatkins\/"}]}},"_links":{"self":[{"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/posts\/3807","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/comments?post=3807"}],"version-history":[{"count":6,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/posts\/3807\/revisions"}],"predecessor-version":[{"id":4829,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/posts\/3807\/revisions\/4829"}],"wp:attachment":[{"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/media?parent=3807"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/categories?post=3807"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/mmcarnot.com\/fr\/wp-json\/wp\/v2\/tags?post=3807"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}